The generator set, comprising a generator and MN210 series diesel engine resiliently mounted on a common baseframe through the high-elastic shaft coupling, fully completed with essential auxiliaries, is an ideal emergency (standby) power supply for small-sized industrial and mining enterprises, hotels, rural areas, etc. Thanks to the under-slung main bearing structure of the MN210 engine, the generator offers low vibration and noise, and high-quality output. The generator is valid in 6 cylinders and 8 cylinders.
Containerized mobile generator powered by the MN210 engine is also available for isolated developing regions which do not have alternative energy sources and for those applications where mobility and fast installation of energy plants are required.
500 to 1350 kW Diesel Generator Sets Model Portfolio Table
Generator Model |
MN500F |
MN600F |
MN800F |
MN1000F |
MN1200F |
MN1350F |
Rated output (kW) |
500 |
600 |
800 |
1000 |
1200 |
1350 |
Engine Model |
MN6210 |
MN6210 |
MN6210 |
MN6210 |
MN8210 |
MN8210 |
Bore x Stroke (mm) |
210 x 300 |
|||||
Engine Type |
Four-Stroke, In-line, direct Injection, Turbocharged, Intercooled |
|||||
Engine Rated Power (kW) |
551 |
662 |
882 |
1103 |
1320 |
1470 |
Speed (rpm) |
50Hz@750, @1000 / 60Hz@900 |
|||||
SFOC (g/kW·h) |
194+3% |
Electrical Performance
Voltage |
Voltage no-load regulation range |
% |
95~105 |
||
Voltage fluctuation rate |
% |
±1 |
|||
Steady state voltage regulating rate |
% |
±2.5 |
|||
Transient voltage regulating rate |
% |
±20~-15 |
|||
Stabilization time |
s |
1 |
|||
Alternator Excitation method |
|
Brushless AVR |
|||
Frequency |
Steady-state frequency (rev.) regulating rate |
% |
5 |
||
Frequency (rev.) fluctuation rate |
% |
±0.5 |
|||
Transient frequency regulating rate |
% |
±10 |
|||
Stabilization time |
s |
< 5 |
|||
Frequency regulating method |
|
Auto / Manual |
|||
Protection |
Over Speed |
115% Nr A, T, S |
Reverse Power |
-9.6% Pn A, T |
|
LO. Pressure |
0.25MPa A, 0.15MPa T, S |
Over Current |
130% In A, T |
||
Freshwater Temperature |
80℃ A, 85℃ T, S |
Over Voltage |
120% Vn A, T |
||
LO. Temperature |
90℃ A |
Overload |
110% In A |
Notes: All engine rating data is based on ISO 3046/1.
Reference conditions: Ambient 45℃, Relative humidity 60%, Intercooler coolant inlet 32 ℃. If test ambient conditions are not the same as the fiducially ambient conditions. The power shall be revised according to ISO3046-1: 2002.
Fuel characteristics: MDO, Lower heat value:42700kj/kg, Consumption tolerance: +5%. Power: An overload of 10% is permitted for one hour every twelve hours of operation.
Characteristics:
Meet with: ISO8528, ISO3046, GB/T13032.
Marine medium speed engine driven, unrestricted service configured, IMO Tier II D2 certified.
Brushless self-excited alternator with AVR, G3 electricity quality.
Application: Power plant set, Emergency automatic start power, Marine Auxiliary power.
As offer customized power plant solutions with multi-options fuels of diesel, LPFO/HFO, biofuel, natural gas, tire pyrolysis oil, etc.
Easy installation, high reliability, low noise, low operating cost, and environmentally friendly.
Outline
Gensets Dimensions(approx.) |
|||||
Model |
A |
B |
C |
D |
Weight |
mm |
mm |
mm |
mm |
(kg) |
|
MN500GF |
5900 |
1577 |
3005 |
1170 |
17000 |
MN600GF |
5950 |
1540 |
2890 |
1170 |
17500 |
MN800GF |
5950 |
1540 |
2890 |
1170 |
18200 |
MN1000GF |
6370 |
1750 |
2994 |
1170 |
19500 |
MN1200GF |
6600 |
1750 |
2994 |
1170 |
21000 |
MN1350GF |
7380 |
1750 |
2994 |
1170 |
22000 |
Remarks: Dimensions and weight are for reference only. For generator set model selection, please make communicate with relevant personnel. The delivery scope for each model engine shall be performed as per the corresponding technical files.