Endowed with ISO9001 and ISO9002 certification for both generator set design and manufacturing, Cummins establishes a robust foundation of quality. We furnish complete quality assurance, shouldering the warranty for generator sets, encompassing the engine, alternator, and control system.
Our expansive nationwide specialized service network guarantees round-the-clock after-sale support, ensuring immediate assistance and a seamless supply of essential parts and accessories. With Megawatt, your satisfaction and uninterrupted performance are our utmost priorities.
Model Portfolio Table
Genset Model |
Standby power |
Prime power |
Engine |
Alternator |
Control system |
||
Kva |
Kw |
Kva |
Kw |
||||
C640D5 |
640 |
512 |
582.5 |
466 |
KTAA19-G6 |
S5L1D-E41 |
PC1.2 |
Ratings definitions:
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with GB.T2820/ISO 8528. The effective oil limited power is in
accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.
Electrical Performance
Prime Power (PRP):
Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with GB.T2820/ISO 8528. A 10% overload capability is available
in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant electrical load for limited hours. Limited-Time Running Power (LTP) is in accordance with GB.T2820/ISO 8528.
Base Load (Continuous) Power (COP):
Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) is in accordance with GB.T2820/ISO 8528, ISO 3046,
AS 2789, DIN 6271 and BS 5514.
Cummins Power Generation C640D5 Diesel Generator Set specifications:
Voltage regulation (no load to full load) |
±1% |
Steady-state voltage variation |
±1% |
Frequency regulation (no load to full load) |
1.40% |
Steady-state frequency variation |
±0.25% |
EMC compatibility |
BS EN61000-6-4 /BS EN61000-6-2 |
Fuel consumption (L/hr) @ 100% load |
131 |
Total coolant capacity (engine and water tank), L |
110.5 |
Bottom oil tank capacity, L |
50 |
Outline
Model |
A |
B |
C |
Weight |
mm |
mm |
mm |
(kg) |
|
C640D5 |
3680 |
1450 |
2050 |
4784 |